8.6

Program example for parameter writing

The following program changes the setting of Pr.7 Acceleration time of station 1 inverter to 3.0 s.
• Acceleration time writing instruction code: H87 (hexadecimal)
• Acceleration time set data: K30 (decimal)
For the instruction codes of parameters, refer to the FR-E800 Instruction Manual (Function).
The reply code at the time of instruction code execution is set to D2. (Refer to
X0
X0F
X1
SW80.0
0
M0
X20
7
M300
11
M301
X100F
13
M302
X100F
22
28
NOTE
• For parameters having numbers 100 and later, change their link parameter extended settings (set them to other than H00).
For the setting values, refer to the parameter list of the FR-E800 Instruction Manual (Function).
• For other functions, refer to the instruction codes (Refer to
M0
Check the data link status of the station 1
PLS M300
SET M301
MOV H87 W102
Write Pr.7 write (H87) to RWw2 and
acceleration time setting data (K30) to RWw3.
MOV K30 W103
Turn on the instruction code execution request (RY0F)
SET Y100F
RST M301
SET M302
Read reply code (RWr2) to D2 when the instruction
MOV W2
D2
code execution completion (RX0F) turns on.
Turn off the instruction code execution request (RY0F)
RST Y100F
RST M302
END