 About setting
• Operation at an error occurrence
Fault description
Pr.502 setting
0
1
Communication line
2
6
0
1, 2
Communication option
6
*1
When the communication returns to normal within the time period set in Pr.500, the communication option error (E.OP1) does not occur.
• Operation after the time in Pr.500 elapses after an error occurrence
Fault description
Pr.502 setting
0
1
Communication line
2
6
0
1, 2
Communication option
itself
6
*2
When an error occurs, the inverter outputs a command to decelerate the motor or shuts off the output, and outputs the fault,
independently of the Pr.500 setting.
*3
When the frequency command source is changed from NET to any other source, frequency commands given from an external device are
enabled.
Operation
*1
Continued
Output shutoff
Output to decelerate and stop
the motor
Operation continued at the set
frequency of Pr.779
Operation
Output shutoff
Output to decelerate and stop
the motor
Operation continued at the set
*3
frequency of Pr.779
*2
Output stop status continues.
Operation continued at the set
*3
frequency of Pr.779
Indication
*1
Normal
"E. 1"
"E. 1" after stop
"CF" warning
Indication
"E.OP1"
"E.OP1" after stop
"CF" warning
*2
"E.1" kept
"CF" warning
INVERTER SETTING
Fault output
*1
Not output
Provided
Provided after stop
Not output
Fault output
Provided
Provided after stop
Not output
*2
Kept provided
Not output
39
4