Mitsubishi Electric 800 Series Instruction Manual page 37

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

Pr.340
Pr.79
setting
setting
0
NET operation mode
1
PU operation mode
2
NET operation mode
*2
10
3, 4
External/PU combined operation mode
6
NET operation mode
7
External operation mode
*1
Operation mode cannot be directly changed between the PU operation mode and Network operation mode.
*2
When a value other than "9999" (selection of automatic restart after instantaneous power failure) is set in Pr.57 Restart coasting time,
the inverter will resume the same operation state which was in before after power has been restored from an instantaneous power failure.
When Pr.340 = "1 or 10", a start command turns off if power failure has occurred and then restored during a start command is on.
*3
Switching between the PU and NET operation modes is available with the key on the operation panel or the X65 signal.
*4
Refer to
page 73
36
INVERTER SETTING
Operation mode at power ON or
power restoration
for a switching method from the network.
Operation mode switchover
Switching between the PU and NET operation mode is enabled.
*3*4
Same as when Pr.340 = "0"
NET operation mode fixed
Same as when Pr.340 = "0"
Switching between the PU and NET operation mode is
*3*4
enabled while running.
Same as when Pr.340 = "0"