7.2.3

Instruction codes

 Instruction code definition
Set the instruction code using a remote register (RWw) (Refer to
The definition read by the instruction code is stored in the remote register (RWr). (Refer to
Item
Operation mode
Output frequency/
*1
speed
Output current
Monitor
Output voltage
Special monitor
Special monitor
selection No.
Read/
Instruction
write
code
H0000: Network operation mode
H0001: External operation mode, External JOG operation mode
Read
H7B
H0002: PU operation mode, External/PU combined operation mode 1 and 2, PUJOG
operation mode
H0000: Network operation mode
Write
HFB
H0001: External operation mode
H0002: PU operation mode (Pr.79 = "6")
H0000 to HFFFF
Read
H6F
Output frequency: Increments 0.01 Hz
H0000 to HFFFF
Read
H70
Output current (hexadecimal): Increments 0.01 A / 0.1 A
H0000 to HFFFF
Read
H71
Output voltage (hexadecimal): Increments 0.1 V
Read
H72
H0000 to HFFFF: Check the data of the monitor selected by the instruction code HF3.
Read
H73
H01 to HFF: Monitor selection data
Refer to monitor code. (Refer to
*2
Write
HF3
page
66.)
page
Description
page
77.)