Chapter 1. Programming Site Data
1.9.2f
Alarm Relays
Refer to Figure 31 on page 80, and complete the following steps to set up the alarm relays of an option card installed in
Slot 1
:
Accessing the Alarm Relay
1. In the Keypad Program, scroll to PROG and press [Enter].
2. In the PROG menu, scroll to GLOBL and press [Enter].
3. In the Global PROGRAM menu, scroll to I/O and press [Enter].
4. Scroll to OPTN and press [Enter].
5. Scroll to Slot 1 and press [Enter].
6. Scroll to the desired Output and press [Enter].
Note: Output letters (A, B, etc.) correspond to the output wiring terminal numbers from top to bottom (e.g. Output A
corresponds to pins 1,2 and 3; Output B corresponds to pins 4, 5 and 6; etc.).
Selecting the Alarm Type
1. Scroll to the desired Alarm type and press [Enter].
2. Do one of the following:
If you selected Off, the XGS868i returns to the I/O window. Go to Procedure Options on the next page.
If you selected High, Low or Fault, proceed to the next step.
3. Scroll to the appropriate mode (Standard or Failsafe), and press [Enter]. (See Chapter 1, Installation, of the Startup
Guide for wiring instructions.)
4. Do one of the following:
If you are using a 1-Channel meter and selected
high or low - proceed to Step 7 on the next page.
fault - proceed to Step 9 on the next page.
If you are using a 2-Channel meter, proceed to the next step.
5. Scroll to the desired Channel option and press [Enter].
30
DigitalFlow™ XGS868i Programming Manual