Huawei ECC500 User Manual page 118

Hide thumbs Also See for ECC500:
Table of Contents

Advertisement

ECC500
User Manual
Category
Reliability
Mechanical
specifications
Table A-2
Table A-2 Technical specifications of the AI/DI module
Category
Environmental
requirements
Input voltage
Power output for
sensors
EMC
Safety regulation
certification
Reliability
Mechanical
specifications
Issue 03 (2020-01-06)
Item
MTBF
Annual repair rate
Service life
Dimensions (H x W x D)
Weight
describes the technical specifications of the AI/DI module.
Item
Operating temperature
Storage temperature
Humidity
Atmospheric pressure
Altitude
Moisture resistance
Others
Working voltage
Rated voltage
N/A
N/A
MTBF
Annual repair rate
Service life
Dimensions (H x W x D)
Copyright © Huawei Technologies Co., Ltd.
A Technical Specifications
Specifications
≥ 100,000 hours
< 1%
> 10 years
44.5 mm x 440 mm x 220 mm
≤ 5 kg
Specifications
–30° C to +65° C
–40° C to +70° C
5%–95% RH (non-condensing)
70–106 kPa
When the altitude is less than or equal
to 3000 m, the device works properly.
When the altitude is greater than 3000
m, the temperature decreases by 1° C
for each additional 300 m.
Damp heat, cyclic: 25–55° C, 95% RH,
48 hours
Free from explosives, electro
conductive dust, and corrosive air
12.8–15 V DC
12 V DC (actual range: 12.6–14.6 V
DC)
Comply with the EN300386 standard.
The monitoring module components
and PCB comply with regulatory
requirements of the IEC60950-1 or
EN60950-1.
≥ 100,000 hours
< 1%
> 10 years
44.5 mm x 175 mm x 100 mm
111

Advertisement

Table of Contents
loading

This manual is also suitable for:

V600r001c01

Table of Contents