Alarm Reference For The Ai/Di Module; Mue06A_Board Not Exist - Huawei ECC500 User Manual

Hide thumbs Also See for ECC500:
Table of Contents

Advertisement

ECC500
User Manual
Attribute
Alarm ID
-
Impact on the System
After this alarm is generated, the device keeps running but prompt maintenance is required.
Possible Causes
Procedure
Step 1 Query and clear the onsite alarm.
Step 2 Check the sensor cable connection.
Step 3 Replace the faulty sensor.
----End
Clearing
This alarm is cleared when the NO dry contact is open or the NC dry contact is closed.

6.2.4 Alarm Reference for the AI/DI Module

6.2.4.1 MUE06A_Board Not Exist

Description
This alarm is generated when cables are not securely connected, the power supply is abnormal,
or the board is faulty.
Attribute
Alarm ID
22656
Issue 03 (2020-01-06)
An alarm is generated onsite.
The cable connection is unreliable.
The sensor is faulty.
For details about the alarms and troubleshooting for the eight ports on the AI/DI module, see the alarm
description and troubleshooting instructions provided for the AI/DI_1 port on the AI/DI expansion card.
Copyright © Huawei Technologies Co., Ltd.
Alarm Severity
The default value is Minor.
Alarm Severity
Set to Major by default.
6 Maintenance and Troubleshooting
Alarm Type
Equipment alarm
Alarm Type
Equipment alarm
78