2.
----End
7.13 How Can I Set Temperature and Humidity Alarm
Thresholds for a T/H Sensor?
Prerequisites
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Monitoring > Temp/Hum Group > Temp/Hum35001 > Running Parameter.
Step 3 Set High Temperature Alarm Point, Low Temperature Alarm Point, High Humidity
Alarm Point, or Low Humidity Alarm Point, and click Submit, as shown in
Issue 03 (2020-01-06)
35001 in Temp/Hum35001 is variable and subject to change with the model, connected collector port,
and device address of the T/H sensor. The displayed value prevails.
Set Name and click Submit, as shown in
Figure 7-14 Changing the T/H sensor name
A T/H sensor has been added to the ECC500.
You have obtained the ECC500 IP address as well as the user name and password for
WebUI login.
You have prepared a PC which is in the same IP address segment as the ECC500 and
connected the PC to the ECC500 over a switch.
35001 in Temp/Hum35001 is variable and subject to change with the model, connected collector port,
and device address of the T/H sensor. The displayed value prevails.