Figure 5-9 Adding a T/H sensor
The setting example indicates that the T/H sensor is connected to the COM5 port of the
RS485 card in slot 3 of the ECC500. If the T/H sensor is connected to another port, set the
slot number for the connected port.
Table 5-3 T/H sensor parameters
Parameter
Communication Board Slot
Communication Board COM
Equipment Address
Timeout
Step 4 Click Add Equipment.
----End
Follow-up Procedure
If the device addition fails, check whether the settings are consistent with the device
parameters.
Issue 03 (2020-01-06)
Setting
Select 3 from the drop-down list box.
Select 5 from the drop-down list box.
In this example, set Equipment Address to 1. Set the
actual device address of the T/H sensor during
operations.
The default timeout interval is 2s. Set the parameter to
the required value.