The cyclic interface sends continually the command while the acyclic one sends it one time
only.
Both interfaces use the following format:
At the moment, the "Command parameter" is not used and it's not evaluated by the EP010.
Its value doesn't care.
2.8.4 Permanent (non volatile) information saving
No information is permanently saved by EP010.
2.8.5 Performance data and conditions
Start up time
Modbus polling rate
2.9
Diagnostic & Troubleshooting
2.9.1 Diagnostic
There are two different type of diagnostic information:
1 local, by FAULT LED flashing
2 remote, by diagnostic information available from FBP.
When the FAULT LED flashes at least one of the following conditions is verified:
#
Meaning
1.
No device communication
2.
Wrong device connected
3.
Device not initialized
4.
Internal configuration map error
5
Wrong parameter number
6.
Wrong parameter value
7.
Command not execute
8.
Watchdog fault
9.
Modbus UART fault
10.
RS 485 driver fault
ABB SACE
WORD
st
1
(Least Significant Word)
nd
2
(Most Significant Word)
Table 6. Command format
max. 3
s]
[
max. 52
ms/query].
[
Description
No device phisically connected OR message CRC error
The connected device Slave ID is NOT the right one
The connected device has not been correctly initialized at the end
of manufacturing (where applicable - see device dependent sections)
Software configuration tables bug
The requested parameter number doesn't exist (only for writing operation)
The parameter value is not allowed (only for writing operation)
The command is correctly received by EP010 but it's not possible
to send it to the device (e.g. the device is not connected)
Start-up diagnostics
Start-up diagnostics
Start-up diagnostics
Table 7. Diagnostic codes
EP010
1SDH000510R0001
DESCRIPTION
Command value
Command parameter
L2388
Page N.
12/28