ABB EP010 User's And Operator's Manual page 21

Modbus / fbp interface
Table of Contents

Advertisement

BINARY OUTPUT
Number of variables
0
Number of bytes
0
Not applicable
ANALOG INPUT
Number of variables
14
Number of bytes
32
#
Name/Description
0 Maximum current
1 L1 run time current
2 L2 run time current
3 L3 run time current
4 N run time current
5 Internal Rog Ground run time current Not available | <0.05In | 1
6 V0 residual voltage
7 V12 line to line voltage
8 V23 line to line voltage
9 V31 line to line voltage
10 Total active power
11 Total reactive power
ANALOG INPUT
Number of variables
2
Number of bytes
4
# Name/Description
0
(Cyclic) Command info - value
1 (Cyclic) Command info - parameter
PARAMETERS
Number of parameters
233
Number of bytes
512
# Name/Description
1 (Acyclic) Command info:
byte 0-1: command value
byte 2-3:
2
Slave ID
3
SW version
ABB SACE
Range
Units Multipler Coding
Not available | <0.05In |
A
{lmin ... lmax}
| > 16ln
Not available | <0.05In |
A
{lmin ... lmax}
| > 16ln
Not available | <0.05In |
A
{lmin ... lmax}
| > 16ln
Not available | <0.05In |
A
{lmin ... lmax}
| > 16ln
Not available | <0.05In |
A
{lmin ... lmax}
| > 16ln
A
Not available | >1.6V |
V
{1.6 ... 150*SQRT(3)}
| >
150*SQRT(3)
Not available | >1.6V |
V
{1.6 ... 150*SQRT(3)}
| >
150*SQRT(3)
Not available | >1.6V |
V
{1.6 ... 150*SQRT(3)}
| >
150*SQRT(3)
Not available | >1.6V |
V
{1.6 ... 150*SQRT(3)}
| >
150*SQRT(3)
Not available||P|<(0.1In*1.6V)|
kW
{(0.1In*1.6V)...(16In*150*
SQRT(3))} |
> (16In*150*SQRT(3)) | <
-(16In*150*SQRT(3))
Not available||P|<(0.1In*1.6V)|
kVAR
{(0.1In*1.6V)...(16In*150*
SQRT(3))}|
> (16In*150*SQRT(3)) | <
-(16In*150*SQRT(3))
Range
No command|CB Open|CB Close|CB Reset |
Trip Reset | Reset Signalling
Reset history measurements |
Reset energy counters |
Reset Events log | restart trigger Datalogger |
Stop Datalogger
Don't care
Range
Units Multipler Coding
No command|CB Open|CB Close|
CB reset | Trip Reset |
Reset Signalling |
Reset history measurements |
Reset energy counters |
Reset Events log|Restart trigger
Datalogger | Stop Datalogger
Don't care
MM.mm
EP010
Lenght
Range
[bytes]
default
2^32-1|0|1|16ln
2
2^32-1|0|1|16ln
2
2^32-1|0|1|16ln
2
2^32-1|0|1|16ln
2
2^32-1|0|1|16ln
2
2^32-1| 0 | 1|
2
10
2^16-1 | 0 | V |
2
150*SQRT(3)
10
2^16-1 | 0 | V |
2
150*SQRT(3)
10
2^16-1 | 0 | V |
2
150*SQRT(3)
10
2^16-1 | 0 | V |
2
150*SQRT(3)
10
2^3-1 | 0 | P
4
(16In*150*SQRT(3))|
-(16In*150*SQRT(3))
10
2^3-1 | 0 | P
4
(16In*150*SQRT(3))|
-(16In*150*SQRT(3))
Units
Multipler
Coding
0 | 1 | 2 | 3 | 4 | 5
6 | 7 | 8 | 9 | 10
Lenght
Range
[bytes]
default
2
0 | 1 | 2 | 3 |
2
4 | 5 | 6 | 7 |
8 | 9 | 10
2
2
MSB = MM
2
LSB = mm
1SDH000510R0001
Notes
Read only PR123 only
Most Significant
Word
Least Significant
Word
Least Significant
Word
Least Significant
Word
Least Significant
Word
Least Significant
Word
2 words (signed)
Format: Low Word |
High Word
2 words (signed)
Format: Low Word |
High Word
Lenght
Range
Notes
[bytes]
default
2
0
Notes
Read only PR123 only
0
0
0
Yes
Yes
Page N.
L2388
20/28

Advertisement

Table of Contents
loading

Table of Contents