Performance Data And Conditions - ABB EP010 User's And Operator's Manual

Modbus / fbp interface
Table of Contents

Advertisement

# Name/Description
1: Protection S electronic disable
2: Protection S electronic curve type
3: Protection I electronic disable
4: Protection G electronic disable
5 15: not used
19 Product execution
20 Protection Unit serial number HI
21 Protection Unit serial number LO
22 CommunicationParameters bitfield:
0 - 7: Slave Address
8: Baud rate
9 - 10: parity
11: Addressing type
12 - 15: not used
23 System disconnection timeout
24 Protection unit nominal current
25 CB type
26 Protection Unit SW version
27 Protection Unit version
DIAGNOSTIC
Number of variables 11
Number of bytes
2
# Name/Description
0 No device communication
1 Wrong device connected
2 Device not initialized
3 Internal configuration map error
4 Wrong parameter number
5 Wrong parameter value
6 Command not executed
7 I/O
8 Watchdog fault
9 Mo driver fault
10 RS 485 driver fault
11 NOT USED
12 NOT USED
13 NOT USED
14 NOT USED
15 NOT USED
3.1.3

Performance data and conditions

Trip Reports and Currents refresh rate
Parameters refresh rate
ABB SACE
Range
Units Multipler Coding
Enabled | Disabled
Definite Time | Inverse Time
Enabled | Disabled
Enabled | Disabled
LSI | LSIG | SI
{1 ... 247}
9600 | 19200
Even | Odd | None
ABB | Standard
{0 ... 6000}, step 1
tenths of ms
100 | 150 | 160 | 200 | 250 |
A
300 | 320 | 400 | 600 | 630 |
800
T4 | T5 | S6
MM.mm
PR222DS | PR222DS/PD
EP010
Lenght
Range
[bytes]
default
0 | 1
Disabled
0 | 1
Inverse Time
0 | 1
Enabled
0 | 1
Disabled
0 | 1 | 2
2
LSI
1 byte for char.
8
(ASCII)
1 byte for char.
8
(ASCII)
2
247
0 | 1
19200
00 | 01 | 10
Even
0 | 1
Standard
2
100
2
100
0 | 1 | 2
2
T4
MSB = MM
2
LSB = mm
0 | 1
2
PR222DS/PD
max. 2 [s]
max. 20 [s]
1SDH000510R0001
Notes
Read only
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Page N.