ABB EP010 User's And Operator's Manual page 17

Modbus / fbp interface
Table of Contents

Advertisement

# Name/Description
5 L1 trip current
6 L2 trip current
7 L3 trip current
8 N trip current
9 Ground trip current
10 CB number of operations
11 CB number of protections trips
12 L number of trips
13 S number of trips
14 I number of trips
15 G number of trips
ANALOG OUTPUT
Number of variables
2
Number of bytes
4
# Name/Description
0 (Cyclic) Command info - value
1 (Cyclic) Command info - parameters
PARAMETERS
Number of parameters 27
Number of bytes
72
# Name/Description
1 (Acyclic) Command info:
byte 0-1: command value
byte 2-3: command parameter
2 Protection L manual trip level
3 Protection L manual trip delay
4 Protection S manual trip level
5 Protection S manual trip delay
6 Protection I manual trip level
7 Protection G manual trip level
8 protection G manual trip delay
9 First bit field:
0: Neutral selection
1: Neutral enabling
2 : Protection S manual disable
3: Protection S manual curve type
4: Protection I manual disable
5: Protection G manual disable
6 - 15: not used
10 date of test (DD/MM/YYY)
11 Protection L electronic trip level
12 Protection L electronic trip delay
13 Protection S electronic trip level
14 Protection S electronic trip delay
15 Protection I electronic trip level
16 Protection G electronic trip level
17 Protection G electronic trip delay
18 First bit field:
0: Prot. L electronic pre-alarm disable
ABB SACE
Range
Units Multipler Coding
A | In
A | In
A | In
A | In
A | In
Range
Units Multipler Coding
No command | CB Open |
CB Close|CB reset|Trip Reset
Don't care
Range
Units Multipler Coding
No Command | CB Open |
CB Close | CB Reset | Trip reset
Don't care
{0.4 ...1}, step 0.02
In
T4-320 | T5-630 | T5-600 UL: 3|
s
6 | 9 | 12
T4 - T5: 3 | 6 | 9 | 18
S6: 3 | 6 | 9 | 18
0 (Disabled) | 0.6 | 1.2 | 1.8 | 3 |
In
3.6 | 4.2 | 5.8 | 6.4 | 7 | 7.6 |
8.2 | 8.8 | 9.4 | 10
0.05 | 0.1 | 0.25 | 0.5
s
T4-320 | T5-630 | T5-600 UL
In
0 (Disabled) | 1.5 | 2.5 | 3 | 4 |
4.5 | 5 | 5.5 | 6.5 | 7 | 7.5 | 8 | 9|
9.5 | 10 | 10.5
T4 - T5
0 (Disabled) | 1.5 | 2.5 | 3 | 4 |
4.5 | 5 | 5.5 | 6.5 | 7 | 7.5 | 8 | 9 |
9.5 | 10.5 | 12
S6
0 (Disabled) | 1.5 | 2.5 | 3 | 4 |
4.5 | 5 | 5.5 | 6.5 | 7 | 7.5 | 8 | 9 |
9.5 | 10.5 | 12
0 (Disabled) | 0.2 | 0.25 | 0.45 |
In
0.55 | 0.75 | 0.8 | 1
0.1 | 0.2 | 0.4 | 0.8
s
50% | 100%
Off (Disabled) | On (Enabled)
Enabled | Disabled
Definite Time | Inverse Time
Enabled | Disabled
Enabled | Disabled
{1 ...31}, {1 ...12}, {0 ... 65535}
{0.4 ... 1}, step 0.01
In
T4-320 | T5-630 | T5-600 UL:
s
{3 ...12}, step 0.5
T4 - T5: {3 ...18}, step 0.5
S6: {3 ...18}, step 0.5
{0.6 ...10}, step 0.1
In
{0.05 ...0.5}, step 0.01
s
T4-320 | T5-630 | T5-600 UL:
In
{1.5 ...10}, step 0.1
In
T4 - T5: {1.5 ...12}, step 0.1
S6: {1.5 ...12}, step 0.1
{0.2 ...1}, step 0.01
In
{0.1 ... 0.8}, step 0.01
s
Enabled | Disabled
EP010
Lenght
Range
[bytes]
default
Lenght
Range
[bytes]
default
0 | 1 | 2 | 3 | 4
2
2
Lenght
Range
[bytes]
default
0 | 1 | 2 | 3 | 4
2
2
100
2
10
2
10
2
100
2
10
2
100
2
100
2
2
0 | 1
0 | 1
0 | 1
0 | 1
0 | 1
0 | 1
6
100
2
10
2
10
2
100
2
10
2
10
2
100
2
100
2
2
0 | 1
1SDH000510R0001
Notes
Read only
2
2
2
2
2
2
2
2
2
2
2
Notes
Notes
Read only
0
0
0.4
Yes
Yes
0
Yes
0.05
Yes
0
Yes
0
Yes
0.1
Yes
Yes
100%
Yes
Off
Yes
Disabled
Yes
Defifite Time
Yes
Disabled
Yes
Disabled
Yes
Yes
1
18
10
0.05
4
4
1
0.8
Enabled
Page N.