Options; Top Cable Entry/Exit Sidecar (Tce) And Top Hat Fascia (Thf) - ABB TLE Scalable Series Installation Manual

40 to 150 kva ul s1
Table of Contents

Advertisement

51/54
6

Options

Warning!
The installation and cabling of the options must be performed by an ABB Service Technician only.
Make sure that the UPS installation is completely powered down.
Refer to the "Safety prescriptions - Installation" described on Chapter 1.

6.1 Top Cable Entry/Exit Sidecar (TCE) and Top Hat Fascia (THF)

Fig. 6.1-1 UPS with "TCE & THF
Top
Tensilock
M5x12
Hat Fascia
B
A
Fig. 6.1-2 Top Hat Fascia (THF) assembling
"Top Cable Entry/Exit Sidecar" (TCE) and "Top Hat Fascia" (THF)
Allows the connection of input and output cables from the top of the UPS.
The "Top Cable Entry/Exit Sidecar" can be located on either side of the UPS
cabinet.
The "Top Cable Entry/Exit Sidecar" is accessibly from lateral panel (see panel "G"
in the Fig. 6.1-3).
Dimensions (W x D x H)
Weight
Screw torque specifications
"Top Hat Fascia" (THF) assembling
Place the structure "Top Hat Fascia - B" over the roof "A" of the UPS
-
cabinet.
Fix the structure "Top Hat Fascia - B" with the appropriate screws.
-
TLE Scalable Series 40 to 150 UL S1
TCE: 3.94"x34.06"x75.00" /100x865x1905mm
THF: 23.62"x34.06"x10.83" /600x865x1237mm
TCE: 88lbs / 40kg
THF: 22lbs / 10kg
Tensilock / Torx M5x12:
UPS Installation Guide / REV-B
26Lb-in / 3Nm