Safety Rules - ABB TLE Scalable Series Installation Manual

40 to 150 kva ul s1
Table of Contents

Advertisement

6/54
1

Safety rules

Save these instructions!
This manual contains important instructions for models TLE Scalable Series 40 to 150 that should be followed
during installation and maintenance of the UPS and Battery.
General
-
Move the UPS in an upright position in its original package to the final destination room.
To lift the cabinets, use a forklift or lifting belts with spreader bars.
-
Check for sufficient floor and elevator loading capacity.
-
Check the integrity of the UPS equipment carefully.
If you notice visible damage, do not install or start the UPS.
Contact your ABB Service Center immediately.
-
WARNING! RISK OF ELECTRICAL SHOCK!
Do not remove covers, there are no user serviceable parts inside.
-
After switching off takes 5 minutes for the DC capacitors to discharge because a lethally high voltage remains
at the terminals of the electrolytic capacitors.
-
UPS's and Battery system require a 12 months periodic maintenance to operate reliably and safely.
This should be performed by qualified service personnel. The UPS contains its own energy source (Battery).
-
The field-wiring outlets may be electrically live, even when the UPS is disconnected from the Utility.
-
Dangerous voltages may be present during Battery operation.
-
The Battery must be disconnected during maintenance or service work.
-
This UPS contains potentially hazardous voltages.
-
Be aware that the Inverter can restart automatically after the Utility voltage is restored.
-
End user must follow applicable regional occupational safety codes/regulations during installation, operation
and equipment maintenance. This may require additional field marking or labelling defining appropriate level
of PPE (Personal Protection Equipment) to reduce the risk of Arc-flash related injuries.
Contact our ABB Service Center for product specific information.
Installation
-
This UPS must be installed and connected only by trained personnel.
-
Verify accurately during Commissioning and Maintenance of the UPS, for the following:
Damaged components, squeezed wires and cables, or not correctly inserted plugs.
-
After removing the sidewalls of the UPS, make sure that all earth connections when reassembling, are correctly
reattached.
-
This UPS is intended for use in a controlled indoor environment free of conductive contaminants and
protected against animals intrusion.
-
WARNING! HIGH LEAKAGE CURRENT TO GROUND:
Ground connection is essential before connecting to AC input!
-
Switching OFF the Unit does not isolate the UPS from the Utility.
-
Do not install the UPS in an excessively humid environment or near water.
-
Avoid spilling liquids on or dropping any foreign object into the UPS.
-
The Unit must be placed in a sufficiently ventilated area; the ambient temperature should not exceed 104°F
(40°C).
-
Optimal Battery life is obtained if the ambient temperature does not exceed 77°F (25°C).
-
It is important that air can move freely around and through the Unit. Do not block the air vents.
-
Avoid locations in direct sunlight or near heat sources.
Storage
-
Store the UPS in a dry location; storage temperature must be within -13°F (-25°C) to 131°F (+55°C).
-
The optimal temperature for Battery storage is 68°F (20°C) to 77°F (25°C) and shall never exceed the range -4°F
(-20°C) to 104°F (40°C).
-
If the Unit is stored for a period exceeding 3 months, the Battery must be recharged periodically (time
depending on storage temperature).
Battery
-
The Battery-voltage is dangerous for person's safety.
-
When replacing the Battery, use the same number, voltage (V) and capacity (Ah).
-
Proper disposal or recycling of the Battery is required.
Refer to your local codes for disposal requirements.
-
Never dispose of Battery in a fire: they may explode.
-
Do not open or mutilate Battery: their contents (electrolyte) may be extremely toxic.
If exposed to electrolyte, wash immediately with plenty of water.
-
Avoid charging in a sealed container.
-
Never short-circuit the Batteries.
When working with Batteries, remove watches, rings or other metal objects and only use insulated tools.
-
In case of air shipment, the cables +/- going to the Battery fuses/terminals shall be disconnected and isolated.
TLE Scalable Series 40 to 150 UL S1
UPS Installation Guide / REV-B