DC link adapter
10.6 Electrical connection
10.6.2

Fixing the cables to the rear cabinet panel

1. Fix the DC link connecting cables directly next to the last component at the rear control
cabinet panel. Use the C-profile rails and the appropriate cable clamps from the Rittal
company. The distance between the C profile rail and the lower side of the component is
approximately 125 mm.
2. Appropriately insulate the cable cores at the connection location before mounting.
Figure 10-4
10.6.3

Cable connection and shield support

In order to simplify installing the DC link connecting cables at the DC link adapter, first fix the
cables to the control cabinet panel (see above).
Required tools:
• Size 6 Allen key to attach the cables
• Suitable tool for hose clamps, e.g. flat-bladed screwdriver
152
Control cabinet panel
DC link adapter
Cores of the DC link connecting cable
C-profile rail from Rittal company (article number 7831.570 / 7831.571)
Cable clamps for C profile rails from the Rittal company.
Fixing the DC link connecting cable to the control cabinet panel, dimensions in mm and
(inch)
High Frequency Drive
System Manual, 10/2020, 6SL3097-5AH10-0BP0