5.3.2.4
Protective conductor connection
Table 5-5
Protective conductor connection for HF Motor Module
5.3.2.5
Busbars
Table 5-6
DC link busbars on the HF Motor Module
5.3.3
Meaning of the LEDs
Table 5-7
Meaning of the LEDs
State
RDY
DC LINK
Off
Off
Green
--
Orange
Red
Orange
Orange
Red
--
Green/red
--
(0.5 Hz)
High Frequency Drive
System Manual, 10/2020, 6SL3097-5AH10-0BP0
Terminals
Protective conductor connection for at‐
taching the equipotential bonding bar
Technical data
Threaded hole M5 / 3 Nm (26.6 lbf in)
Description, cause
The electronics power supply is missing or outside the
permissible tolerance range.
The component is ready for operation. Cyclic DRIVE-CLiQ
communication is taking place.
The component is ready for operation. Cyclic DRIVE-CLiQ
communication is taking place.
The DC link voltage is present.
The component is ready for operation. Cyclic DRIVE-CLiQ
communication is taking place.
The DC link voltage is too high.
DRIVE-CLiQ communication is being established.
This component has at least one fault.
Note:
The LED is controlled irrespective of the corresponding
messages being reconfigured.
Firmware is being downloaded.
Technical data
Threaded hole: M8
Tightening torque: 13 Nm
For ring cable lugs without insulation (Page 178)
Remedy
–
–
–
Check the line supply voltage.
–
Resolve and acknowledge the
fault.
–
High Frequency Modules
5.3 HF Motor Module
47