Cabinet design and EMC
12.3 24 V DC supply voltage
Using the 24 V connector
• A 24 V connector should be inserted onto the 24 V busbar between each Active Line Module
Booksize, HF Motor Module, HF Choke Module, HF Damping Module and DC link component.
• Attachment and removal are only permissible in a de-energized state.
• A maximum of 5 unplugging and plugging cycles is permissible.
Note
The 24 V connectors must be attached before the drive line-up is commissioned.
12.3.3

Typical 24 V current consumption of the components

A separate 24 V power supply must be used for the SINAMICS S120 drive line-up.
The following table can be used to calculate the 24 V DC power supply. The values for typical
current consumption are used as a basis for configuration.
Table 12-1
Component
Control Unit
NCU730.3
without load
each digital output
Active Interface Modules
120 kW Booksize
132 KW, 160 kW chassis
Active Line Modules
120 kW Booksize
132 KW chassis
HF Motor Module 225 A
HF Choke Module 225 A
HF Damping Module 225 A
Braking Module
174
Overview of the 24 V DC current consumption
Typical current consumption [A
1.9
0.1
1.2
0.17
1.8
1.1
0.8
1.6
0.9
0.5
System Manual, 10/2020, 6SL3097-5AH10-0BP0
]