Braking Modules
7.2 Braking Module Booksize Compact
7.2.9
Configuration instructions
DC link capacitance
When configuring the drive line-up, please note that only one Braking Module Booksize Compact
may be used per complete 500 µF DC link capacitance.
Table 7-17
DC link capacitance in µF
900
2400
9,800
DC link cable
In a multi-row or distributed drive line-up, the DC links are connected to each other via a DC link
cable. When using a Braking Module Booksize Compact in the drive line-up, this cable must not
be longer than 10 m. In all cases, the DC link cable must have low impedance and a cross-section
of at least 10 mm
Parallel operation
During configuration of parallel operation for Braking Modules Booksize Compact,
dimensioning can only take 90% of the specified braking power into account. Only the peak
powers may be added without derating.
The following applies when connecting Braking Modules in parallel:
P
N total
4 x P
P
max total
120
Configuration examples
.
2
= 0.9 x total P
of single devices
N
= 0.9 x sum (4 x P
) of single devices
N total
N
= total P
of single devices
max
Max. number of Braking Modules
1
4
19
System Manual, 10/2020, 6SL3097-5AH10-0BP0
High Frequency Drive