Optional) Setting The Pressure Difference Control - Huawei NetCol5000-C030 User Manual

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C030:
Table of Contents

Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Parameter
Temperatur
e setpoint
Humidity
setpoint
Step 4 Go back to the home screen, and tap Running > Device Details > T/H sensor to
check that the cold aisle 1 temperature and humidity are displayed and the values
are reasonable.
Figure 4-5 Cold aisle temperature and humidity
----End

4.5.2 (Optional) Setting the Pressure Difference Control

Prerequisites
If the differential pressure sensor is installed, perform the following operations
accordingly. If the differential pressure sensor is not installed, skip this part.
Procedure
Step 1 On the home screen, choose Settings > System Settings > Indoor fan, set Air-
side difference pressure sensor type to 0–50 Pa.
Issue 04 (2021-03-15)
Description
After the temperature and
humidity control type and the
temperature value under this
type are set, the device
performs cooling or heating
based on the settings.
After the temperature and
humidity control type and the
humidity value under this type
are set, the device performs
humidifying or dehumidifying
based on the settings.
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
Setting Rule
Set this parameter as required.
● Return air temperature: 26–
35°C recommended
● Supply air temperature: 18–
24°C recommended
● Cold aisle temperature: 18–
24°C recommended
● Hot aisle temperature: 26–
35°C recommended
Set this parameter as required.
40%–60% RH recommended
95