Huawei NetCol5000-C030 User Manual page 114

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C030:
Table of Contents

Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Context
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > SNMP Settings.
4-8
Figure 4-8 Setting SNMP communications parameters
Step 2 Set SNMP Version based on site requirements, and then tap Submit.
Step 3 Set Read Community and Write Community.
1.
2.
Issue 04 (2021-03-15)
To set communications parameters, log in as the admin user.
This section is suitable only for SNMP. Skip this section if you use Modbus.
Record the values entered in this section. They will be used when you access a
smart cooling product to an NMS.
One smart cooling product supports concurrent access of up to 6 NMSs
through SNMP.
is displayed.
If you set SNMP Version to ALL or SNMPv1&v2c, you can set Read
Community and Write Community by performing
If you set SNMP Version to ALL or SNMPv3, you can add SNMPv3 users by
performing
Step
4.
Tap the text box after Read Community, as shown in
Community as planned, tap
Figure 4-9 Setting the read community
Tap the text box after Write Community, as shown in
Community as planned, tap
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
Step
Figure
, and then tap Submit.
and then tap Submit.
Figure
3.
4-9. Set Read
Figure
4-10. Set Write
106

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol5000-c032Netcol5000-c065

Table of Contents