User Manual
Exercise caution because the device is still energized after it is shut down on the
screen of the display module.
Step 2 Open the rear door, remove the air filter, and turn off the general switch of the
smart cooling product.
Step 3 Disconnect the interconnection terminals from the actuator and ensure that the
actuator cable is separated from the smart cooling product.
1.
2.
3.
Step 4 Install the new water valve actuator by performing
the actuator cable, and then secure the cable using cable ties.
Step 5 Open the rear door, install the air filter, and turn on the power switch of the smart
cooling product.
The shaft of the new actuator must be installed in the same position where the
old actuator shaft is installed.
----End
Issue 04 (2021-03-15)
NO TICE
Press the actuator button, as shown by (1) in
Figure 6-19 Removing a chilled water valve actuator
Manually set the chilled water valve opening to the maximum (100%), as
shown by (2) in
Figure
Insert a Phillips screwdriver into the hole right in front of the actuator, and
turn the screwdriver in the specified direction to unscrew the actuator, as
shown by (3) in
Figure
NO TICE
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
6-19.
6-19.
Figure
6-19.
Step 3.3
to
Step
2, connect