Specifications
Number of input points
Insulation method
Rated input voltage
Input voltage distortion
Rated input current
Inrush current
Operating voltage range
Maximum number of
simultaneous input
points
ON voltage/ON current
OFF voltage/OFF current
Input impedance
OFFON
Response
time
ONOFF
Common terminal
arrangement
Operation indication
External connection
method
Applicable wire size
Applicable solderless
terminal
Current consumption
External dimensions
Weight
*1
Check the specifications of the sensor or switches to be connected to the QX10.
*2
The following shows the derating chart.
A0J2-E32A
32 points
Photocoupler
100-120VAC, 50/60Hz
10mA
Approx. 8mA (100VAC, 60Hz)
(100VAC, 60Hz)
Approx. 7mA (100VAC, 50Hz)
Max. 300mA, within 0.3ms
(with 132VAC)
85 to 132VAC
(50/60Hz±5%)
100% (32 points)
simultaneously ON
80VAC or more/5mA or more
80VAC or more/6mA or more
40VAC or less/4mA or less
Approx. 10k (60Hz),
Approx. 12k (50Hz)
15ms or less (6ms TYP.)
35ms or less (16ms TYP.)
16 points/common
(Common terminal: TB17, TB34)
Available (Turning ON the input
turns LED ON)
36-point terminal block
connector
(M3 × 6 screws)
2
0.75 to 2mm
1.25-3, 1.25-YS3A,
2-S3, 2-YS3A,
(Sleeved solderless terminals
V1.25-3, V1.25-YS3A,
V2-S3, V2-YS3A
0.105A (TYP. All points are ON.)
0.05A (TYP. All points are ON.)
250(H) × 132(W) × 41(D) mm
98(H) × 27.4(W) × 90(D) mm
0.68kg
Derating chart
100
90
80
ON
ratio
70
60
50
40
0
10
20
Ambient temperature
: Compatible,
QX10
Compatibility
16 points
Photocoupler
100-120VAC, 50/60Hz
Within 5%
Max. 200mA, within 1ms
(with 132VAC)
85 to 132VAC
(50/60Hz±3Hz)
*2
Refer to the derating chart.
(50Hz, 60Hz)
30VAC or less/1.7mA or less
(50Hz, 60Hz)
Approx. 12k (60Hz),
Approx. 15k (50Hz)
15ms or less
(100VAC 50Hz, 60Hz)
15ms or less
(100VAC 50Hz, 60Hz)
16 points/common
(Common terminal: TB17)
ON indication (LED)
18-point terminal block
(M3 × 6 screws)
2
0.3 to 0.75mm
core
(Outside diameter: 2.8mm or
less)
R1.25-3
cannot be used.)
0.17kg
120VAC
132VAC
30
40
50 55
: Partially changed, × : Incompatible
Precautions for replacement
When seventeen or more points
are used, use two QX10 modules.
Rated input current is smaller.
Use it within the range shown in the
derating chart.
*1
OFF current is smaller.
Input impedance is greater.
×
×
Wiring change is required.
×
×