I/O MODULES REPLACEMENT
(3) Specifications comparison between A0J2-E24S and QY22
Specifications
Number of output points
Insulation method
Rated load voltage
Maximum load voltage
Maximum load current
Minimum load voltage/
current
Maximum inrush current
Leakage current at OFF
Maximum voltage drop at
ON
OFFON
Response
time
ONOFF
Surge suppressor
Common terminal
arrangement
Operation indication
Fuse rating
Fuse blown indication
External connection
method
Applicable wire size
Applicable solderless
terminal
Current consumption
External dimensions
Weight
*1
Consider the characteristics of the triac and observe the necessary precautions by referring to Section 3.3 (3) before
replacing the modules.
*2
Install a fuse for each external terminal point to prevent the burnout of the external devices and modules during load shorts.
In addition, when a fuse blown indication is necessary, configure an external circuit.
3
- 19
A0J2-E24S
24 points
Photocoupler
100 to 240VAC, 40 to 70Hz
264VAC
0.6A/point, 2.4A/common
24VAC 100mA
100VAC 10mA
240VAC 10mA
20A 10ms or less
8A 100ms or less
1.5mA (120VAC 60Hz)
3mA (240VAC 60Hz)
1.5V or less (100 to 600mA)
1.8V or less (100mA or less)
2V or less (10 to 50mA)
1ms or less
0.5 cycle + 1ms or less
(Rated load, resistance load)
CR absorber
(0.022µF + 47)
8 points/common
(Common terminal: TB9, TB19,
TB29)
Available (Turning ON the output
turns LED ON)
High speed type fuse 3.2A
(1/common) HP-32
Available
(When a fuse blown occurs, LED
is lit, and
a signal is output to the CPU)
36-point terminal block
connector
(M3 × 6 screws)
2
0.75 to 2mm
1.25-3, 1.25-YS3A,
2-S3, 2-YS3A,
(Sleeved solderless terminals
V1.25-3, V1.25-YS3A,
V2-S3, V2-YS3A
400mA (TYP. All points are ON.)
0.25A (MAX. All points are ON.)
250(H) × 132(W) × 41(D) mm
98(H) × 27.4(W) × 112.3(D) mm
0.70kg
*1
: Compatible,
QY22
Compatibility
16 points
Photocoupler
100 to 240VAC
50/60Hz±5%
264VAC
0.6A/point, 4.8A/common
24VAC 100mA
100VAC 25mA
240VAC 25mA
20A 1 cycle or less
1.5mA or less
(During 120V 60Hz)
3mA or less
(During 240V 60Hz)
1.5V or less
1ms or less
1ms + 0.5 cycle or less
CR absorber
16 points/common
(Common terminal: TB17)
ON indication (LED)
None
18-point terminal block
(M3 × 6 screws)
2
0.3 to 0.75mm
core
(Outside diameter: 2.8mm or
less)
R1.25-3
cannot be used.)
0.40kg
: Partially changed, ×: Incompatible
Precautions for replacement
When seventeen or more points
are used, use two QY22 modules.
The frequency will be low. Check
the specifications of external
devices.
The minimum load current is
greater. Use caution on selecting
the load to use.
As the common changes from
three commons to a common,
wiring with a different voltage for
each common is not possible.
×
*2
The fuse is not built in.
×
×
×
Wiring change is required.
×
×
The dimensions are different.