Mitsubishi Electric MELSEC-A0J2H Series Handbook page 204

Table of Contents

Advertisement

(4) Specifications comparison between A0J2E-E24R and interface module (SC-A0JQIF24R)
Specifications
Number of output points
Insulation method
24VDC 2A (Resistance load)/point
Rated switching voltage/
current
Minimum switching load
Maximum switching
voltage
Leakage current at OFF
Maximum switching
frequency
Mechanical life
Rated switching voltage/current load
(COS=0.7) 200,000 times or more
Electrical life
(COS=0.35) 200,000 times or more
(L/R=7ms) 200,000 times or more
OFFON
Response
time
ONOFF
External
Voltage
supply
power
(Relay coil
Current
driving
power)
Surge suppressor
Fuse
Fuse blown indication
Relay socket
Common terminal
arrangement
(Common terminal: TB9, TB19, TB29)
Operation indication
(Turning ON the output turns LED ON)
Specifications
5VDC internal current
consumption
External connection
36-point terminal block connector
method
Applicable wire size
(Applicable tightening torque 69N•cm)
Applicable solderless
terminal
Weight
External dimensions
*1
The value when using the output module, QX41Y41P, QY41P, etc.
App
- 9
A0J2E-E24R
24 points
Photocoupler
240VAC 2A (COS=1)/point
5A/common
5VDC 1mA
250VAC 125VDC
3600 times/hr
20 million times or more
200,000 times or more
200VAC 1.5A, 240VAC 1A
200VAC 0.75A, 240VAC 0.5A
24VDC 1A, 100VDC 0.1A
10ms or less
12ms or less
24VDC±10%
Ripple voltage 4Vp-p or less
220mA
(24VDC All points are ON.)
Varistor (387 to 473V)
Available (8A)MF51NM8 or
FGMA250V8A
None
None
8 points/common
Available
A0J2E-E24R
0.145A (TYP. All points are ON.)
(M3 × 6 screws)
2
0.75 to 2mm
1.25-3, 1.25-YS3A,
2-S3, 2-YS3A,
V1.25-3, V1.25-YS3A,
V2-S3, V2-YS3A
0.75kg
250(H) × 132(W) × 41(D) mm
SC-A0JQIF24R output
specifications
24 points
None
24VDC 2A (Resistance load)/point
240VAC 2A (COS=1)/point
5A/common
5VDC 1mA
250VAC 125VDC
3600 times/hr
20 million times or more
Rated switching voltage/current load
200,000 times or more
200VAC 1.5A, 240VAC 1A
(COS=0.7) 200,000 times or more
200VAC 0.75A, 240VAC 0.5A
(COS=0.35) 200,000 times or more
24VDC 1A, 100VDC 0.1A
(L/R=7ms) 200,000 times or more
9ms or less
11ms or less
24VDC±10%
Ripple voltage 4Vp-p or less
230mA
(24VDC All points are ON.)
None
None
None
8 points/common
(Common terminal: TB9, TB19, TB29)
None
SC-A0JQIF24R
36-point terminal block connector
(M3 × 6 screws)
2
0.75 to 2mm
(Applicable tightening torque 69N•cm)
1.25-3, 1.25-YS3A,
2-S3, 2-YS3A,
V1.25-3, V1.25-YS3A,
V2-S3, V2-YS3A
0.47kg
*5
182(H) × 132(W) × 41(D)mm
: Compatible,
: Partially changed, × : Incompatible
Compatibility
Precautions for replacement
Photocoupler is provided on Q series
output module side.
In combination with Q series output
module:
10ms or less (6ms TYP.)
In combination with Q series output
module:
12ms or less (6ms TYP.)
×
The varistor is not built in.
×
The fuse is not built in.
Operation indication can be checked
with Q series output module.
Compatibility
Precautions for replacement
Also consider the weight of fixed
stand of programmable controller.
Check the dimensions since they
depend on the installation type
×
(building-up/horizontal/separate
type).
*1
*1
*2
*3
*4

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec q series

Table of Contents