10
REPLACING THE SPECIAL FUNCTION MODULE
(d) Buffer memory addresses comparisons
Buffer memory allocation is different, so the sequence program must be changed.
Refer to the Digital -Analog Converter Module User's Manual for details regarding the buffer memory
and sequence program.
Address
(decimal)
0
CH1 Digital value
1
CH2 Digital value
2
CH1 voltage set value check code
3
CH2 voltage set value check code
4
CH1 current set value check code
5
CH2 current set value check code
10
- 13
A0J2-62DA
Name
Read/Write
R/W
Q62DAN
Address
Name
(decimal)
0
D/A conversion enable/disable
1
CH1 Digital value
2
CH2 Digital value
3
4
5
System area
to
10
11
CH1 Set value check code
12
CH2 Set value check code
13
to
System area
18
19
Error code
20
Setting range (CH1 to CH2)
21
System area
Offset gain setting mode
22
Offset setting
Offset gain setting mode
23
Gain setting
24
Offset/gain adjustment value
25
to
System area
157
158
Mode movement setting
159
160
to
System area
199
200
Pass data classification setting
201
System area
202
CH1 Industrial shipment settings offset value
203
CH1 Industrial shipment settings gain value
204
CH2 Industrial shipment settings offset value
205
CH2 Industrial shipment settings gain value
206
CH1 User range setting offset value
207
CH1 User range setting gain value
208
CH2 User range setting offset value
209
CH2 User range setting gain value
Read/Write