Technical data
13.1 Technical specifications for POM
Technical specifications for POM4320 rear panel mounting
product brand name
Product designation
General technical data:
Type of load
Equipment marking / acc. to DIN EN 81346-2
Supply voltage:
Type of voltage / of the supply voltage
Supply voltage / at AC / rated value
Relative negative tolerance / of the supply volt-
age
Relative positive tolerance / of the supply volt-
age
Supply voltage frequency / 1 / rated value
Supply voltage frequency / 2 / rated value
Relative symmetrical tolerance / of the supply
voltage frequency
Power capacity
of the module / with delta connection / at 40
°C / with fan / maximum
maximum permissible
Switching capacity current / per phase / maxi-
mum
Short-time withstand current (SCCR) / acc. to UL
508A
Design of the electrical isolation
Recovery time / after power failure / typical
Type of electrical connection / for supply voltage
Type of connectable conductor cross-section
for supply voltage / solid
for supply voltage / finely stranded / with core
end processing
for AWG conductors / for supply voltage
124
SIPLUS
POM4320 rear panel mounting
(IEC)
Ohmic load
Q
AC
400 V
10 %
30 %
50 Hz
60 Hz
5 %
69.1 kW
69.1 kW
83 A
-
Optocoupler and/or protective impedance between main circuit and
PELV
1 s
Terminal, 3-pin
1x (1.5 ... 50 mm²)
1x (1.5 ... 35 mm²)
1x (16 ... 1)
Operating Instructions, 11/2015, A5E35452705A/002
POM4320 rear panel mounting
(UL)
64.8 kW
64.8 kW
80 A
50 kA