Monitoring Functions; Line Supply Voltage Monitoring; Rotating-Field Test; Monitoring Of The 24 V Dc Supply Voltage - Siemens SIPLUS HCS Operating Instructions Manual

Hide thumbs Also See for SIPLUS HCS:
Table of Contents

Advertisement

Functions

9.6 Monitoring functions

9.6
Monitoring functions
9.6.1

Line supply voltage monitoring

Line supply voltage monitoring
The Power Output Module (POM) can be operated in TN systems and TT systems. The
admissible line supply voltage is between 360 V and 520 V AC. The active line voltage is
measured and monitored for each POM and each phase. The actual voltage measurement is
reported to the user (see section Cyclic input data (Page 85)).
If the voltage lies outside the admissible range, an error message will be generated (see
section Process and system messages, error handling (Page 99)) and heater operation
stops. Heating can only be switched on again when the voltage has returned to the
admissible range.
NOTICE
Excessive voltages can damage the device
It is the responsibility of the user to ensure compliance with the maximum voltage limits.
9.6.2

Rotating-field test

The rotating field is tested for connecting the phase voltages of each POM. The POM
requires a clockwise rotating field. Otherwise an error message is generated.
Note
The heating system can also operate with a counter-clockwise rotating field. However, it is
not possible to diagnose a defective emitter at a channel setpoint of 100 %.
9.6.3

Monitoring of the 24 V DC supply voltage

The 24 V DC supply voltage is monitored on the CIM. If the 24 V fails, the power outputs of
the POMs are automatically deactivated. There is no manufacturer-specific diagnostics
alarm in the case of failure of the 24 V supply. Instead, the PROFINET/PROFIBUS controller
detects and signals the failure of the HCS system or modules.
78
Operating Instructions, 11/2015, A5E35452705A/002
SIPLUS HCS4300

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hcs4300

Table of Contents