Communications
10.2 Acyclic data exchange
Dataset 200 "measured values"
Data POM 1
Data POM 2
...
Data for POM 24
Definition is via an array [1..24] with one element of type "Structure". This comprises two
elements of type "Byte" and four elements of type "Word".
The POM number corresponds to the array index.
The length of the dataset corresponds to the number of POMs that are used.
Dataset 201 "versions"
CIM / PM
POM 1
POM 2
...
POM 24
All firmware versions contain one element of type "Char" and three elements of type "Byte".
The hardware versions are all of type "Byte".
Definition of the POM versions is via an array [1...24] with one element of type "Structure".
The POM number corresponds to the array index.
The length of the dataset corresponds to the number of POMs that are used. The entry for
CIM with PM is always available, even if the PM is not plugged in.
92
Byte
Description
0
Internal temperature
1
Reserved
2,3
Frequency (with one decimal place)
4,5
Voltage measured value L12 (with one decimal place)
6,7
Voltage measured value L23 (with one decimal place)
8,9
Voltage measured value L31 (with one decimal place)
...
...
...
...
...
...
Byte
Description
0...3
FW version of CIM fieldbus controller
4...7
FW version of CIM HCS master
8
HW version of CIM
9
HW version of PM
10...13
FW version of PM
14...17
Firmware version POM 1
18
Hardware version triac POM 1
19
Hardware version fuse POM 1
...
...
...
...
...
...
Operating Instructions, 11/2015, A5E35452705A/002
SIPLUS HCS4300