13.2

Technical specifications for CIM

product brand name
Product designation
General technical data:
Equipment marking / acc. to DIN EN 81346-2
Number of slots
Type of power output / connectable
Supply voltage:
Type of voltage / of the supply voltage
Supply voltage / 1 / at DC / rated value
Relative negative tolerance / of the supply volt-
age
Relative positive tolerance / of the supply volt-
age
Active power consumption
Type of electrical connection / for supply voltage Connector 2x2-pin with tension spring connection
Type of connectable conductor cross-section
for supply voltage / solid
for supply voltage / finely stranded / with core
end processing
for AWG conductors / for supply voltage
Communication:
Design of the interface
Protocol / is supported
PROFIBUS DP protocol
PROFINET IO protocol
Transfer rate
with PROFIBUS DP / maximum
with PROFINET IO / maximum
Type of electrical connection
of the PROFIBUS interface
of the PROFINET interface
Display:
Number of status displays
Display version / as status display by LED
SIPLUS HCS4300
Operating Instructions, 11/2015, A5E35452705A/002
SIPLUS
CIM4310 PROFINET
K
1
POM4320
DC
24 V
20 %
20 %
3 W
1x (0.2 ... 2.5 mm²)
1x (0.2 ... 2.5 mm²)
1x (26 ... 12)
PROFINET IO
No
Yes
-
100 Mbit/s
-
2 x RJ45
3
LED green = ready, LED yellow = heating on/off, LED red = error
display
Technical data
13.2 Technical specifications for CIM
CIM4310 PROFIBUS
PROFIBUS DP
Yes
No
12 Mbit/s
-
9-pin D-Sub socket
-