Section 5
Monitoring
5.3.3.1

Setting procedure on the IED

The parameters for breaker monitoring (SSCBR) can be set via Protection and Control Manager
(PCM600).
Common base IED values for primary current (
power (
GlobalBaseSel : It is used to select a GBASVAL function for reference of base values.
PhSel : It is used to select different phase values.
IBase : Base phase current in primary A. This current is used as reference for current settings.
InitCounterVal : Initial value for number of operations
InitAccCurrPwr : Initial value for accumulated I^CurrExponent integr over CB open travel time
value.
InitInactDays : Initial value for inactive days.
InactiveAlHrs : Alarm time for inactive days counter in hours.
InitCBRemLife : Initial value for remaining life estimates.
InactiveAlDays : Alarm level for inactive days counter.
OpenTimeCorr : Correction factor for circuit breaker opening travel time.
CloseTimeCorr : Correction factor for circuit breaker closing travel time.
tTrOpenAlm : Setting of alarm level for opening travel time.
tTrCloseAlm : Setting of alarm level for closing travel time.
OperAlmLevel : Alarm limit for number of mechanical operations.
OperLOLevel : Lockout limit for number of mechanical operations.
CurrExponent : Current exponent setting for energy calculation. It varies for different types of
circuit breakers. This factor ranges from
AccStopCurr : RMS current setting below which calculation of energy accumulation stops. It is
given as a percentage of
ContTrCorr : Correction factor for time difference in auxiliary and main contacts' opening time.
AlmAccCurrPwr : Setting of alarm level for accumulated energy.
46
Since there is no current measurement in SAM600-IO, evaluation of the
following parameters are not possible in the circuit breaker condition
monitoring function (SSCBR):
Circuit breaker status
Remaining life of the circuit breaker
Contact erosion estimation
Circuit breaker contact travel time
Ensure that OPENPOS, CLOSEPOS, INVDPOS, CBLIFEAL, IPOWALPH,
IPOWLOPH, TRVTOPAL and TRVTCLAL signals are not used in SAM600–IO.
SBase ) are set in Global base values for settings function GBASVAL.
IBase .
© Copyright 2017 ABB. All rights reserved
IBase ), primary voltage ( UBase ) and primary
0.5 to 3.0 .
1MRK 511 445-UEN B
GUID-4E895FEA-74BF-4B11-A239-0574F8FF5188 v5
Switchgear control unit SAM600-IO
Application manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion sam600-io

Table of Contents