Section 9
Basic IED functions
The DataObject Mod of the Root LD.LNN0 can be set on the LHMI under Main menu/Test/
Function test modes/Communication/Station communication/IEC61850 LD0 LLN0/
LD0LLN0:1 to
When the setting of the DataObject Mod is changed at this level, all Logical Nodes inside the
logical device update their own behavior according to IEC61850-7-4. The supported values of
the function block TESTMODE are described in
Edition 2 . When the function block TESTMODE is in test mode the Start LED on the LHMI is
turned on with steady light.
The parameter
Function test modes/Communication/Station Communication
The parameter Mod can be set on the LHMI to the same values as for the DataObject Mod of
the Root LD.LNN0 to
Function test modes/ Differential protection/GeneratorDiff(87G,3Id/I>)/ GENPDIF(87G,3Id/
I>):1.
It is possible that the behavior of the function block TESTMODE is also influenced by other
sources as well, independent of the mode communicated via the IEC61850-8-1 station bus. For
example the insertion of the test handle into the test switch with its auxiliary contact is
connected to a BI on the IED and further inside the configuration to the input IED_TEST on the
function block TESTMODE. Another example is when loss of Service Values appears, or as
explained above the setting via the LHMI.
When setting via PST or LHMI the parameter
the function is not executed and the behavior (beh) is set to
override it. When a behavior of a function is
keeps its current state.
The IEC 61850-7-4 gives a detailed overview over all aspects of the test mode and other states
of mode and behavior. The status of a function block behavior
the Main menu/Test/Function status/Function group/Function block descriptive name/LN
name/Outputs.
When the
control commands with a test bit are accepted.
When the
bit are accepted. Outputs to the process via a non-IEC 61850 link data are blocked by the
function block. Only process-related outputs on function blocks related to primary
equipment are blocked. If there is an XCBR function block used, the outputs
and
When the
are accepted. Outputs to the process via a non-IEC 61850 link data are blocked by the
function block. In addition, the function block can be blocked when their
This can be done if the function block has a block input.
72
To be able to set the function block TESTMODE remotely, the setting via path
on LHMI and in PST: Main menu/Configuration/Communication/ Station
Communication/IEC61850-8-1/IEC61850-8-1:1
set to
Off . The possible values of the parameter RemoteModControl are Off ,
Maintenance or All levels . The Off value denies all access to function block
TESTMODE from remote,
originator (orCat) is
On , Off , TestBlocked , Test or Blocked .
Mod of any specific function block can be configured under Main menu/Test/
On , Off , TestBlocked , Test or Blocked . For Example, Main menu/ Test/
When IEC 61850 Mod of a function is set to
LHMI will be set to flashing to indicate the abnormal operation of the IED.
Beh of a function block is set to Test , the function block is not blocked and all
Beh of a function block is set to Test/blocked , all control commands with a test
EXC_Close are blocked.
Beh of a function block is set to Blocked , all control commands with a test bit
© Copyright 2017 ABB. All rights reserved
Maintenance requires that the category of the
Maintenance and All levels allow any orCat.
Communication protocol manual, IEC 61850
Operation of any function in an IED is set to Off ,
Off the function will not execute. The related Mod
Off or Blocked , the Start LED on the
1MRK 511 445-UEN B
RemoteModControl may not be
Off and it is not possible to
Beh is shown on the LHMI under
EXC_Open
Beh is blocked .
Switchgear control unit SAM600-IO
Application manual