Minimum Cross-Sections For Pe (Protective Conductor)/Equipotential; Bonding Conductor - Siemens 6SN1123-1AA00-0DA2 Configuration Manual

Simodrive 611 series drive converter
Table of Contents

Advertisement

02.12
05.01
7.2.3
Minimum cross–sections for PE (protective conductor)/equipotential

bonding conductor

Table 7-4
© Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
Minimum cross–sections for PE (protective conductor)
P
I
rated
rated
[kW]
[A]
5
7
10
14
28
40
16
23
36
52
55
79
80
115
120
173
7 Line Supply Connection
7.2 Voltage matching
PE
PE
2
[mm
]
[AWG/kcmil]
1.5
16
4
14
10
8
4/10
10
16
6
16
4
25
3
50
1/0
7-209