Siemens 6SN1123-1AA00-0DA2 Configuration Manual page 234

Simodrive 611 series drive converter
Table of Contents

Advertisement

02.12
05.01
Caution
The connections/terminals may not be interchanged:
S
S
If this is not observed, the line filter could be damaged.
Table 7-14
Assigning the wideband filters to the I/R modules
Filter
Line filter
components
16 kW
Rated AC current
30 A
Supply voltage
3–ph. 380 V – 10% ... 3–ph. 480 V AC + 10% (TN line supply)
Order number
6SL3000–
0BE21–6AAV
Mounting position
Wall or base/floor mounting, refer to Fig. 7-13
Dimensions (W x H x D),
130x480x150
approx.
Module width
Refer to dimension drawings, Chapter 12
Weight, filter
9 kg
Power loss
70 W
Connection
16/10 mm
/1.5 Nm
PE, M5 studs/
3 Nm
Terminals
L1, L2, L3, PE
Line supply connection
(line)
Terminals
U, V, W
Load connection (load)
4)
I
fuse
35 A
rated
Permissible
ambient temperature
S
Operation
[°C]
S
–25 ... +70
Storage/transport [°C]
Cooler
Natural ventilation
Degree of protection to
IP20
EN 60529 (IEC 60529)
DIN EN 61800-3 (IEC
Limit value Class C2
61800-3)/VDE 0160-103 ra-
dio interference suppres-
sion
1) The permissible supply voltage of the system depends on the infeed module used.
2) For ring cable lugs to DIN 46234.
3) The first data applies for pin–type cable lugs, the second data applies for finely–stranded conductors without end sleeves
4) The fuse used must have this rated current. Recommendations for the fuses, refer to Table 7-6.
© Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
Incoming line supply cable to LINE/NETZ L1, L2, L3
Outgoing cable to the line reactor to LOAD/LAST U, V, W
I/RF module
I/RF module
16/21 kW
36/47 kW
Line filter
36 kW
67 A
6SL3000–
0BE23–6AAV
130x480x245
16 kg
90 W
2 3)
2
50 mm
/6 Nm
PE, M8
2)
2)
studs/13 Nm
L1, L2, L3, PE
U, V, W
80 A
0 ... +40; maximum +55 at 0.6 • P
7 Line Supply Connection
7.4 Line filters for I/R and UI modules
I/RF module
I/RF module
55/71 kW
80/104 kW
Line filter
Line filter
55 kW
80 kW
103 A
150 A
; 50...60 Hz $10%
1)
6SL3000–
6SL3000–
0BE25–5AAV
0BE28–0AAV
130x480x260
200x480x260
19 kg
22 kg
110 W
150 W
2
2
50 mm
95 mm
/6 Nm
/15 Nm
PE, M8
PE, M8
2)
2)
studs/13 Nm
studs/13 Nm
L1, L2, L3, PE
L1, L2, L3, PE
U, V, W
U, V, W
125 A
160 A
of the l/R module
rated
I/RF module
120/156 kW
Line filter
120 kW
225 A
6SL3000–
0BE31–2AAV
300x480x260
34,5 kg
200 W
2
95 mm
/15 Nm
PE, M8 studs/
2)
13 Nm
L1, L2, L3, PE
U, V, W
250 A
7-233