Cable
grommet
(blank)
Ambient
temperature
sensor
Condensation
plug
Figure 9-1: Bottom plate connections
The mains fuse holders with modular fuses for the product are shown in Figure 9-2.
Figure 9-3 shows the location of the power supply terminals for the mains supply.
Figure 9-2: Mains fuse holders with
fuses (front - inside)
To ensure a safe connection to the power supply, follow these steps:
Disconnect the power supply to the product at the external switch or circuit
breaker before accessing internal components.
Route the mains supply cable through the 25 mm cable gland on the bottom
of the product.
The outer sheath of the mains supply cable shall continue into the equipment
as far as possible, so that reinforced insulation is maintained between the
operator and mains supply.
The mains supply shall be connected so that the protective earth wire is the
last wire to take the strain and break free in the event of the cord being
pulled.
MA-005 - Minitrans Installation Manual - Rev 4.5
Earth
Modular
fuse
holder
Figure 9-3: Mains fuse holders with terminal
connections (top - outside)
Power-in (gland)
M8 earth
connection
Cable
grommets
Neutral
Live
13-Aug-20
Page 30 of 86