GE Kelman Minitrans Installation Manual page 83

Transformer oil dissolved gas and moisture monitor
Hide thumbs Also See for Kelman Minitrans:
Table of Contents

Advertisement

M.3.5
Remove the cradle lock
The locks on the exterior isolators must be disengaged after transit, but before the
product is powered on.
M.3.5.1 Bottom isolators
Loosen the nut at the front of the bottom isolator with a 10 mm nut spinner as shown
in Figure M-37.
Loosen the outer nut at the back of the bottom isolator with a 10 mm spanner as
shown in Figure M-38.
Figure M-37: Loosen isolator front nut with nut
spinner
Loosen the inner M6 nut of the bottom isolator with a 10 mm spanner and remove all
fittings as shown in Figure M-39.
Pull down on the bottom locks to remove them.
Figure M-39: Bottom isolator with fittings removed
Repeat for the other bottom isolator.
MA-005 - Minitrans Installation Manual - Rev 4.5
Note: Remove and retain this nut for future use.
Inner
M6 nut
Lug
Figure M-38: Loosen isolator rear outer nut with
spanner
Note: Retain nut and washer for future use.
Note: No nuts or
washers required
Spanner on outer
M6 nut
Large washer
13-Aug-20
Page 83 of 86