Mitsubishi Electric Melsec Q Series User Manual page 60

Hide thumbs Also See for Melsec Q Series:
Table of Contents

Advertisement

6 Buffer memory
6.3.8 Average current (Un \ G218, 219)
Stores the Average current.
For procedure for storing the Average current using phase wire system, refer to section 4.2.1 (2).
(1) Details of stored data
(a) Storage format
Data are stored as double-word 32-bit signed binary in the buffer memory.
- Data range:0 to 99999990 (0 to 99999.990 A)
*Restrictions for measured data including resolution and measuring range, refer to section 4.2.1.
(b) Unit
×10
-3
A
(c) Update timing
It will be updated every measuring cycle (250 ms).
6.3.9 Maximum value of electric current demand (Un \ G220,221), minimum value of electric current demand
(Un \ G226,227)
Stores the max./min. values of the electric current demand among phases.
For procedure for storing the max./min. the electric current demand using phase wire system, refer to
section 4.2.1 (2).
(1) Details of stored data
(a) Storage format
Data are stored as double-word 32-bit signed binary in the buffer memory.
- Data range: 0 to 99999990 (0 to 99999.990 A)
*Restrictions for measured data including resolution and measuring range, refer to section 4.2.1.
(b) Unit
×10
-3
A
(c) Update timing
It will be updated every measuring cycle (250 ms) if it exceeds the current max. value or goes
under the current min. value.
*Unit is fixed.