21

Output Contacts

Introduction
Like the G3's input terminals, the G3's output contacts can be programmed to perform a variety of
functions. On the standard G3, the available output terminals are RCHA/RCHB, LOWA/LOWB, and
FLA/FLB/FLC. Another form C output contact is available on option cards INV3-COM-B and INV3-
COM-D.
Connections
TERMINAL STRIP
P24
FLA
FLC
FLB
RCHA
RCHC
LOWA
LOWC
CC
24 VDC LED
With the drive programmed with factory default values, the above connection example will illuminate the LED when the drive is
outputting a non-zero frequency.
P24' is a 24 VDC 50 mA supply that can be used to power coils or control devices.
Do not connect 'CC' to ground
The G3's output contacts are rated for 30 VDC, 1 amp; 250 VAC, 1 amp inductive, 2 amp resistive.
Programming
The function associated with the FLA/FLB/FLC, RCHA/RCHC, and LOWA/LOWC terminals is assigned
by putting one of the following Setting Values in "RCH" Contacts Function, "LOW" Contacts Function,
and "FL" Contacts Function (in TERMINAL SELECTION PARAMETERS group) respectively. The
value programmed for "FL" terminal applies to the normally open contact.
44
For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-
2192