Toshiba G3 Workbook page 47

Applications workbook
Table of Contents

Advertisement

Setting
Comments
Value
40
Contact closes when drive is running at or above 0.01 Hz.
41
Contact closes when drive is not running at or above 0.01 Hz.
42
Contact closes when drive is faulted on a "severe" fault (not retryable)
43
Contact closes when drive is not faulted on a "severe" fault
44
Contact closes when drive is tripped on Overload or one of the Overcurrents
45
Contact closes when drive is not tripped on Overload or one of the Overcurrents
46
Auto-bypass control. Contact closes to energize coil of output contactor. See Application Guideline #16
47
Opposite logic state of above
48
Auto-bypass control. Contact closes to energize coil of bypass contactor. See Application Guideline # 16
49
Opposite logic state of above
50
Contact closes when drive's cooling fan(s) is on.
51
Contact closes when drive's cooling fan(s) is not on.
52
Contact closes when drive is jogging
53
Contact closes when drive is not jogging
54
Contact closes when drive is getting RUN/STOP command from the keypad
55
Contact closes when drive is not getting RUN/STOP command from the keypad
56
Contact closes when drive run time is greater than or equal to time programmed into Cumulative Run Timer Alarm
Setting (PROTECTION PARAMETERS group)
57
Contact closes when drive run time is not greater than or equal to time programmed into Cumulative Run Timer Alarm
Setting (PROTECTION PARAMETERS group)
58
Contact closes when drive has a Communication Error
59
Contact closes when drive does not have a Communication Error
60
Contact changes state when drive goes through 0.0 Hz to change direction. Contact is closed/open during forward/reverse
run. Contact maintains current condition at 0.0 Hz when decel is complete after a stop command.
61
Contact changes state when drive goes through 0.0 Hz to change direction. Contact is open/closed during forward/reverse
run. Contact maintains current condition at 0.0 Hz when decel is complete after a stop command.
62
Contact closes when drive has a run command and ST-CC is made
63
Contact closes when drive does not have a run command
For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-