(1)
The dancer trims the drive's output frequency a maximum of +/- 12.5 % of the Maximum Output
Frequency
(2)
The following is an example of how to adjust the RX Bias/Gain:
Suppose dancer output is 1-5 volts. Set the micro switch next to the phone jack on the control board in the
'5" position. Suppose that the dancer output voltage when the dancer is in the desired position is 2.5
volts. 2.5/5.0 = 0.50 or 50 percent.
SETTING PARAMETERS group). After the following Super
will automatically adjust its output frequency to maintain the dancer's output voltage
position) at 2.5 volts.
(3)
These are suggestions and will have to be field-adjusted. See Application Guideline 24 for PID
information
With the RX Bias/Gain programmed as above, the drive will increase its output frequency when the
dancer voltage is above 2.5 volts; it will decrease its output frequency whenever the dancer voltage is
below 2.5 volts. If this relationship is the opposite of what is desired for a particular dancer, program RX
Reference Point #2 Frequency (FREQUENCY SETTING PARAMETERS group)
to '-60'. Now the drive will increase its output frequency whenever the dancer voltage is below 2.5 volts
and decrease its output frequency whenever the dancer voltage is above 2.5 volts.
Additional Programming
KEYSTROKE
LOCAL/REMOTE
READ/WRITE
READ/WRITE hold down
LOCAL/REMOTE
READ/WRITE
down arrow
down arrow
READ/WRITE
up arrow until
READ/WRITE
arrows until
READ/WRITE
PRG
(4)
Example of how to determine the "new value"
Suppose "64" was the value found here. Converted to BCD, this is 0110 0100 (0010 binary is 6 decimal, 0100 binary
is 4 decimal). Process dancer control is turned on by setting the leftmost bit to '1', so the new BCD values will be
1110 0100,
which is E4 in hex. Use the up arrow to adjust the 64 to read E4.
For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-
Enter 50 into RX Reference Setting Point #1 (FREQUENCY
RESULTING DISPLAY
OUTPUT FREQUENCY
OUTPUT FREQUENCY
OUTPUT FREQUENCY
GROUP: SUPERUSER
RAMF
RAM
EEP
0380
04B9
something
(4)
new value
04B9 alternating with new value, then 04B9
OUTPUT FREQUENCY
2192
User programming is done, the drive
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
(and therefore
63