Power cable connection – frame sizes C and D (connector covers removed)
3 N·m
(25 lbf·in)
La/
La/
UDC+ UDC-
U2 V2 W2
AC supply cable
(from WFU-xx)
DC Supply cable
Cable clamp on bare
shield 1.5 N·m (13 lbf·in)
Lb/
UDC+
Lb/
U1 V1 W1
UDC+
R- R+
Braking resistor cable
Below cable clamp, cover
bare shield with insulating
tape
15 N·m
(130 lbf·in)
3 N·m
(25 lbf·in)
3 N·m
(25 lbf·in)
15 N·m
(130 lbf·in)
3 N·m
(25 lbf·in)
Cable clamp on bare
shield 1.5 N·m (13 lbf·in)
Screw lug detail
15 N·m (11 lbf·ft)
Direct lug connection
Instead of using the screw lugs
included, the conductors of power
cables can be connected to the drive
terminals by removing the screw
lugs and using crimp lugs.
53