Control cable grounding

The shields of all control cables connected to the JCU Control Unit must be
grounded at the control cable clamp plate. Use four M4 screws to fasten the plate as
shown below left. The plate can be fitted either at the top or bottom of the regen
supply module.
The shields should be continuous as close to the terminals of the JCU as possible.
Only remove the outer jacket of the cable at the cable clamp so that the clamp
presses on the bare shield. At the terminal block, use shrink tubing or insulating tape
to contain any stray strands. The shield (especially in case of multiple shields) can
also be terminated with a lug and fastened with a screw at the clamp plate. Leave
the other end of the shield unconnected or ground it indirectly via a few nanofarads
high-frequency capacitor (e.g. 3.3 nF / 630 V). The shield can also be grounded
directly at both ends if they are in the same ground line with no significant voltage
drop between the end points.
Keep any signal wire pairs twisted as close to the terminals as possible. Twisting the
wire with its return wire reduces disturbances caused by inductive coupling.
Mounting the clamp plate
0.7 N·m
(6.2 lbf·in)
Electrical installation
1.5 N·m
(13 lbf·in)
Use shrink tubing or
tape to contain
strands
If shielded cable is in
use, remove outer
jacket of cable at
clamp to expose cable
shield.