46
A diagram of the cable routing is below.

Control cable ducts

Planning the electrical installation
Input cable
DC Supply cable
Regen
Regen
filter
supply
module
module
AC supply
cable
min 200 mm (8")
24 V 230 V
Not allowed unless the 24 V
cable is insulated for 230 V or
insulated with an insulation
sleeving for 230 V.
min 200 mm (8")
Control cables
min 500 mm (20")
90°
AC/DC Supply cable
Motor cable
Braking resistor cable
Lead 24 V and 230 V control
cables in separate ducts inside
the cabinet.
DC supply cable
Braking resistor cable
min 300 mm (12")
min 300 mm (12")
min 300 mm (12")
24 V
230 V