Installation of options

Options such as fieldbus adapters and I/O extensions are inserted into slots on the
JCU Control Unit. See page
manual for specific installation and wiring instructions.

Removing EMC and varistor screws from the regen filter module

On IT (ungrounded) systems, and corner grounded TN systems, the EMC and
varistor screws must be removed from the regen filter module.
Note: When the internal EMC filter is disconnected, the regen supply is not EMC
compatible.
1. Remove the cover of the regen filter module.
2. Remove the two screws labeled FILTER and one screw labeled VARISTOR. The
3. Re-install the cover.
WFU-01, WFU-02
WFU-21, WFU-22
WFU-11, WFU-21 and WFU-22 only: Remove the fan.
locations of the screws are shows in the pictures below.
WFU-11, WFU-21 and WFU-22 only: Re-install the fan.
FILTER
FILTER
FILTER
VARISTOR
25
for the available slots; see the appropriate option
VARISTOR
FILTER
Electrical installation
57