Connecting The Control Cables; Control Connections To The Jcu Control Unit - ABB ACSM1 Hardware Manual

Regen supply modules
Hide thumbs Also See for ACSM1:
Table of Contents

Advertisement

54

Connecting the control cables

Control connections to the JCU Control Unit

Notes:
*Total maximum current: 200 mA
1)
WFU-xx cooling fan control
2)
WFU-xx temperature supervision
The wiring shown is for demonstrative
purposes only. Refer to the
appropriate Firmware Manual for
default I/O assignments.
Further information of the usage of the
connectors and jumpers are given in
the text; more details are available in
the chapter
Technical
data.
Wire sizes and tightening torques:
2
X2: 0.5 ... 2.5 mm
(24...12 AWG).
Torque: 0.5 N·m (5 lbf·in)
X3, X4, X5, X6:
2
0.5 ... 1.5 mm
(28...14 AWG).
Torque: 0.3 N·m (3 lbf·in)
Order of terminal headers and
jumpers
X1 (2-pole)
X2 (3-pole)
X3 (4 × 4-pole,
1 × 3-pole)
X4 (1 × 7-pole,
1 × 2-pole,
1 × 3-pole)
J1
J2
J3
X5 (3-pole)
X6 (4-pole,
orange)
Electrical installation
External power input
24 V DC, 1.6 A
Relay output
250 V AC / 30 V DC
2 A
+24 V DC*
Digital I/O ground
Digital input 1: Stop/start (EXT2)
Digital input 2: EXT1/EXT2
+24 V DC*
Digital I/O ground
Digital input 3: Fault reset
Digital input 4: Force stop
+24 V DC*
Digital I/O ground
Digital input 5: Not connected
Digital input 6: Not connected
+24 V DC*
Digital I/O ground
Digital input/output 1: Fan control signal (output)
Digital input/output 2: Running (output)
+24 V DC*
Digital I/O ground
Digital input/output 3: Fault (output)
Reference voltage (+)
Reference voltage (–)
Ground
Analogue input 1 (Not connected)
Current/Voltage
Analogue input 2 (Not connected)
AI1 current/voltage selection
AI2 current/voltage selection
Thermistor input
Ground
Analogue output 1 (current)
Analogue output 2 (voltage)
Ground
Drive-to-drive link termination
Drive-to-drive link. See separate section below.
Not in use. Both circuits must be closed for the
regen supply module to start. See separate
section below.
Control panel connection
Memory unit connection
X1
+24VI
1
GND
2
X2
NO
1
COM
2
NC
3
X3
+24VD
1
DGND
2
DI1
3
DI2
4
+24VD
5
DGND
6
DI3
7
DI4
8
+24VD
9
DGND
10
DI5
11
DI6
12
+24VD
13
DGND
14
DIO1
15
DIO2
16
+24VD
17
DGND
18
DIO3
19
24 V DC
X4
+VREF
1
-VREF
2
AGND
3
AI1+
4
AI1-
5
AI2+
6
AI2-
7
J1
J2
TH
8
AGND
9
AO1 (I)
10
AO2 (U)
11
AGND
12
X5
J3
B
1
A
2
BGND
3
X6
OUT1
1
OUT2
2
IN1
3
IN2
4
1)
WFU
X3.14
X3.15
2)
WFU
X4.8
X4.9