6.8.1.5. Preparing cables for cable entries with cable glands
Prepare the cables with an outer cable screen for EMC bonding with the metal enclosure of the
cabinet as illustrated (Fig. 72).
1
2
3
Fig. 72. Preparing control cables for cable glands
PRODUCT
ACS5000W gen. 2
Key:
(1)
Outer cable sheath
(2)
Cable gland
4
(3)
Conductor insulation removed to expose cable shield
(4)
Plate
(5)
Conductor screen extension to be connected to PE terminal
5