2.4. Main circuit breaker protection device
The main circuit breaker (MCB) is a major protection device of the drive. If a serious fault occurs
in the drive, the MCB must disconnect the main power supply to the drive immediately. The main
power supply must be disconnected without delay on an open or trip command from the drive
to prevent hazard to the personnel and further damage to the equipment. The MCB is located
on the primary side of the converter transformer.
1
5
Key:
(1)
Main power supply
(2)
MCB control interface
(3)
Higher-level control system
(4)
Local MCB control
(5)
MCB
Fig. 3. Drive system overview
The MCB is defined as a switching device to disconnect the power supply whenever required by
the process or when a fault occurs. Typical devices used as MCBs are:
–
Vacuum circuit breakers
–
SF6 circuit breakers
–
Fused contactors or motor control centers
A dedicated protection relay is used for:
–
Transformer primary cable protection
–
Transformer protection (if applicable)
–
Transformer secondary cable protection (if applicable)
–
Backing up the drive protection
In general, these protective measures are not included in the drive as provided by ABB.