Starting The Drive System After An Emergency-Off; Fig. 87. Detail Of Local Control Panel - ABB ACS5000 User Manual

Water-cooled (generation 2)
Hide thumbs Also See for ACS5000:
Table of Contents

Advertisement

SUPPLY
OFF
ON
1
2
ALARM
RESET
FAULT
EMERGENCY OFF
EMERGENCY OFF

Fig. 87. Detail of local control panel

8.9.2. Starting the drive system after an emergency-off

You need to reset the EMERGENCY OFF button after each use, ie, when the RESET EMERGENCY
OFF button is flashing. The button is either on the local control panel of the COU door or at an
external location that is linked to the emergency-off circuit.
Referring to Fig. 87:
1. Verify that the reason for the emergency stop has been resolved.
2. Turn the red EMERGENCY OFF push button in the direction of the arrows until the button
unlatches and returns to the up position.
3. Press the RESET EMERGENCY OFF push button.
The flashing light of the button turns off, the emergency-off safety relay of the drive is reset,
and the drive status message changes to ReadyOn.
1 L ->
0.0 rpm
StateINU
ReadyOn
MOTOR SP
0.00 rpm
POWER
0.0 kW
4. Connect the main power supply to the drive and start the drive according to Section 8.8,
"Starting the drive", page 129.
PRODUCT
ACS5000W gen. 2
Key:
SUPPLY OFF push button
(1)
RESET EMERGENCY OFF push button
(2)
EMERGENCY OFF latching push button
(3)
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS799208 E01
OPERATION
REV.
LANG.
PAGE
J
en
134/186