8.9.1. Stopping the drive in an emergency

The EMERGENCY OFF push button (Fig. 87) on the local control panel (Fig. 85) is a
hardwired fail-safe control switch that immediately disconnects the drive from the
main power supply when pressed. When you activate an emergency off:
MCB opens
Drive system coasts down
DC-link of the drive discharges
Status line indication of the CDP control panel alternates between EmergeOff
and NotReadyOn.
1 L ->
StateINU
MOTOR SP
POWER
Emergency-off reset push button flashes.
Main power supply off push button flashes.
CAUTION
Hazardous voltage. The EMERGENCY OFF push button DOES NOT disconnect the
auxiliary power supply from the drive.
→ Avoid contact with live parts
Referring to Fig. 87:
1. Press the EMERGENCY OFF push button for the drive system:
On the local control panel of the COU door
At an external location that is linked to the emergency-off circuit
The emergency stop activates and the EMERGENCY OFF button locks in the open position.
While the stop is active, the RESET EMERGENCY OFF and SUPPLY OFF buttons flash.
NOTE – If the drive is at a standstill when you press the emergency off-push button, you will not
be able to connect the drive to the main power supply or start the drive.
PRODUCT
ACS5000W gen. 2
600.0 rpm
EmergeOff
NotReadyOn
0.00 rpm
0.0 kW
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS799208 E01
OPERATION
REV.
LANG.
PAGE
J
en
133/186