6. Electrical installation
6.1. Safety
DANGER
Hazardous voltage! Risk of DEATH or life-threatening injury!
→ Qualified personnel only, who have a thorough knowledge of relevant electrical
codes, site, and equipment requirements.
→ DO NOT switch on main and auxiliary power supplies without ABB consent.
→ Take preventive measures to ensure power remains off during the installation.
→ Obtain consent from ABB commissioning personnel at end of the installation to
switch on the power
6.2. Overview
Electrical installation includes the following tasks:
–
Grounding
–
Internal wiring
–
Cable entries
–
Power cables, ground cables, equipotential bonding conductor
–
Auxiliary power cables and control cables
6.3. Cable requirements
6.3.1. Power cables
For information on the requirements for power cables, ground cable and equipotential bonding
conductor, see:
–
"ACS5000 power cable specification", 3BHS215798 E01
–
"Power cables engineering guideline", 3BHS542290 E01
6.3.2. Auxiliary and control cables
NOTICE
Risk of false signals! Power supply cables can disrupt signals in control cables.
→ DO NOT lay control cables in parallel to the power supply cables; if this cannot be avoided, a
minimum distance of 30 cm must be maintained between control and power supply cables.
→ Cross control and power supply cables at an angle of 90°
For information on the requirements for the auxiliary power cable and the control cables, see
"Auxiliary power and control cables guideline", 3BHS813742 E01.